· Module 11

PLC DC motor speed control — complete worked companion lesson

Dr. Redmond R. Shamshiri
Assistant Professor of Robotics · University of Southern Denmark (SDU)

Implement a documented start/stop sequence, encoder scaling and a discrete PI speed loop with actuator limits. This is an authored companion lab; no unverified YouTube video is attached.

Learning Objectives

  • Specify the PLC I/O and run-state logic.
  • Convert encoder counts into rpm and a speed reference into a bounded drive command.
  • Implement and explain discrete PI control with conditional integration.
  • Test stop priority, communication loss, saturation recovery and restart prevention.

Purpose and system boundary

Build a teaching speed-control loop: HMI reference → PLC PI controller → rated motor drive → DC motor → encoder → PLC. The PLC sends a command; the drive switches motor power. This companion lesson is independent of any unverified video-specific hardware configuration.

Use a secured, low-energy motor rig and a current-limited supply. An emergency stop must act through the appropriate independent hardwired protective circuit or rated drive safety function; ordinary PLC application logic and a web/HMI button do not establish a safety-rated stop.

I/O and state design

SignalMeaningInitial/fault behavior
StartRequestMomentary operator startDoes not auto-restart after power recovery
StopOKPermissive stop chain feedbackFalse removes run request
DriveReady / DriveFaultDrive statusFault latches a diagnostic
EncoderCountSigned, decoded output-shaft countMissing/implausible data inhibits control
SpeedSet_rpmBounded HMI referenceClamped to validated rig limit
DriveEnable / SpeedCommandSeparate enable and demandDisabled and zero demand
\[Run_{k+1}=Ready\land StopOK\land\neg Fault\land(Start\lor Run_k)\]

Stop and fault dominate Start. Reset clears the fault only after its cause is removed; it does not start the motor. Define a separate deliberate Start action.

Encoder speed and command scaling

\[n_k=\frac{60(N_k-N_{k-1})}{N_{rev}T_s}\]

Nrev is effective decoded counts per output-shaft revolution, including quadrature mode and gearing; Ts is seconds. Handle count rollover and timestamp jitter. A nominal PLC scan period is not a substitute for measured elapsed time.

\[RawCommand=Raw_{min}+\operatorname{clip}(u,0,1)(Raw_{max}-Raw_{min})\]

The raw command endpoints must come from the actual drive/interface manual. They are not universal PLC constants. A 0–10 V output might encode a 0–100% demand, but speed still depends on the drive mode and feedback implementation.

Discrete PI with conditional anti-windup

\[e_k=r_k-n_k,\quad I^*=I_{k-1}+K_iT_s e_k,\quad u^*=K_pe_k+I^*\]
\[u_k=\operatorname{clip}(u^*,0,1)\]

Accept I* only when the output is unsaturated, or when the error would drive a saturated output back toward its valid range. Otherwise retain the previous integral. When Run is false, apply zero command and reset the integrator for this teaching design.

// Illustrative Structured Text; adapt types and I/O to the PLC.
IF NOT Run THEN
    Integral := 0.0;
    SpeedDemand := 0.0;
ELSE
    Error := SetpointRpm - MeasuredRpm;
    CandidateI := Integral + Ki * SampleSeconds * Error;
    CandidateU := Kp * Error + CandidateI;
    IF ((CandidateU >= 0.0) AND (CandidateU <= 1.0))
       OR ((CandidateU > 1.0) AND (Error < 0.0))
       OR ((CandidateU < 0.0) AND (Error > 0.0)) THEN
        Integral := CandidateI;
    END_IF;
    SpeedDemand := LIMIT(0.0, Kp * Error + Integral, 1.0);
END_IF;

This is a conceptual unidirectional loop, not a complete machine program. Add input validity checks, drive handshake, current/temperature limits and a measured sample time appropriate to the actual rig.

Numerical example

Assume 2,048 effective counts/revolution and 512 counts measured in 0.25 s: measured speed = 60 rpm. With reference 80 rpm, Kp = 0.01 duty/rpm, Ki = 0.02 duty/(rpm·s), Ts = 0.02 s and previous integral 0.10, the proposed integral is 0.108 and output is 0.308, or 30.8% demand. The 0.25 s speed-estimation window and 20 ms controller period are different; analyze the measurement delay before tuning aggressively.

If demand is constrained to 0–100% and the motor cannot reach the reference under load, continuing to integrate positive error creates windup. Confirm saturation handling by lowering the reference after a deliberately limited run.

Commissioning sequence

  • Document wiring, drive mode, protective circuit, current limit and validated maximum speed.
  • With power disabled, test truth-table transitions and restart prevention in simulation.
  • Verify encoder count direction and counts/revolution at low energy.
  • Test the open-loop drive demand, then start with low proportional gain and zero integral gain.
  • Log reference, measured rpm, error, requested/applied duty, integral and sample timestamps.
  • Add integral action gradually and test load steps, stop priority, stale feedback and saturation recovery.

Evidence: I/O table, state transition trace, a time plot for reference/speed/demand, and a failure-test table including observed stop time. Acceptance thresholds must be defined for the actual apparatus before testing.

Exercise with solution

A 1,000-count/revolution encoder produces 100 counts in 0.1 s. Reference is 90 rpm. Kp = 0.005 duty/rpm, Ki = 0.01 duty/(rpm·s), Ts = 0.02 s and previous integral = 0.20. Calculate the next unsaturated PI output.

Show calculation

Measured speed = 60 rpm; error = 30 rpm. Integral candidate = 0.20 + 0.01×0.02×30 = 0.206. Output = 0.005×30 + 0.206 = 0.356, or 35.6%. It is inside the assumed 0–1 range, so accept the integral update.

Summary

PLC scan, latching and interlocks: keep units, assumptions and timing explicit. Check the numerical model against an independent observation before using it in a larger system.

Practical PLC & HMI Automation: Build a Mini Factory · Dr. Redmond R. Shamshiri · University of Southern Denmark (SDU)