Skip to content
Adaptive AgroTech NetworkUniversity of Southern Denmark · SDU Drone Center
Course2026
← Practical Motor Control for Robotics | ESP32 & PLCModule 12

PLC to VFD: Start, Set Speed, Read Faults | Lecture 12

InstructorDr. Redmond R. Shamshiri
AffiliationAssistant Professor of Robotics · University of Southern Denmark (SDU)
Study time35 minutes
Watch & study

Lecture video

Open on YouTube ↗

Video unavailable here? Watch on YouTube. Captions and playback speed are available in the player.

Study companion. These editable notes, worked examples and exercises supplement the source material. They are not a verbatim video transcript or a reproduction of the book.

Study PLC to VFD: Start, Set Speed, Read Faults | Lecture 12. Use the accompanying model, numerical example and practical task to connect the topic to a measurable engineering result. Notes are original supplemental material, not a transcript.

Learning Objectives

  • Explain the role of plc supervision of an ac variable-frequency drive in the engineering system.
  • Calculate the worked quantity with consistent units.
  • Design a measurement that can reveal an implementation failure.

Study guide

Original companion notes. These notes support the topic of this lesson. They are not a transcript or a claim about the exact contents, hardware settings or examples in the video.

Lesson focus: PLC to VFD: Start, Set Speed, Read Faults | Lecture 12

Reproduce one named failure, identify its earliest observable symptom and verify recovery with a timed log.

PLC supervision of an AC variable-frequency drive

A variable-frequency drive controls an AC motor through its own power stage and configured motor model. The PLC requests enable, direction and speed while the drive enforces its configured limits and reports status. Verify whether the reference means frequency, speed or percentage, and distinguish induction-motor slip from synchronous speed.

Model, units and assumptions

\[n_s=\frac{120f}{P},\qquad n=(1-s)n_s\]

ns is synchronous speed in rpm, f is electrical frequency in Hz, P is motor pole count and s is induction-motor slip as a fraction. The second relation is for an induction motor; it is not a universal law for every motor/drive combination.

Worked engineering example

A four-pole motor at 50 Hz has synchronous speed 1,500 rpm. At 3% slip its rotor speed is approximately1,455 rpm. A drive can report measured or estimated speed; check the configured source before treating a register as independent feedback.

Practical task and evidence

Apply the following procedure to the topic of this lesson: PLC to VFD: Start, Set Speed, Read Faults | Lecture 12.

  • Record the motor nameplate and drive mode, command source, reference units and permitted acceleration/deceleration.
  • Verify Ready, Running and Fault handshakes at a low-energy commissioning condition.
  • Test stop requests and communication timeout behavior using the drive manufacturer’s documented settings.

Submit: a diagram or interface table, a short timestamped dataset, the calculation with units, and a paragraph explaining the largest observed limitation.

Check your understanding

Question. For a four-pole motor at 40 Hz, find synchronous speed.

Show worked answer

1,200 rpm; actual induction-motor rotor speed also depends on slip.

Extension. Change one assumption in the model and explain which measurement would reveal that it no longer holds.

Summary

PLC supervision of an AC variable-frequency drive: keep units, assumptions and timing explicit. Check the numerical model against an independent observation before using it in a larger system.

Suggested Reading & Resources