How Do You Detect a Broken Sensor Wire in a 4–20 mA Loop?
The 4 mA low endpoint in a current loop provides a live zero. A reading near zero current can flag a loss of loop continuity or power.
The key idea
A receiver can evaluate the loop's fault range separately from its measurement span. An open conductor and an unpowered transmitter may both produce very low current, so the reading alone cannot pinpoint the cause.
What to remember
- Use the instrument's specified fault thresholds.
- Preserve a fault indication rather than scaling the reading as process data.
Check your understanding
A linear 4–20 mA level sensor reports 0 mA. Should the display show an empty tank?
Show the explanation
No. The configured empty level corresponds to 4 mA. Report a loop fault and investigate continuity and supply.